Call Us 800.362.8774 Call Us 866-294-5847 Contact Training Training Training WeatherTRAK Login WaterCompass Login AppManager Login

Knowledgebase

    FM200 Troubleshooting - Communication Issues

    Gain an understanding of the basics of FM200 communication issues.

    PDF es:

    FM200 Communication Issues

    The following steps will provide guidance on troubleshooting FM200 flow monitors experiencing intermittent or no communication. Do Not leave the site until communication has been verified.

     

    Troubleshooting No Communication and Intermittent Communication issues

    Step 1: Replace the batteries in the FM200 flow monitor

    1. Continue to step 2 once the battery replacement is complete. Please see Battery Replacement Guide for instructions

    Reminder: DO NOT  move or remove the sensor from the register during the battery replacement.

     

    Step 2: Perform a visual inspection of the Antenna and cable connection

    1. Is the antenna securely connected to the flow monitor?
      • If yes, move to Step 2-B.
      • If no, connect the antenna and move to step 2-B.
    2. Is the antenna physically damaged?
      • If yes, move to Step 4.
      • If no, continue to Step 2-C.
    3. Is the antenna cable physically damaged?
      • If yes, move to Step 4.
      • If no, continue to Step 2-D.
    4. Is the antenna mounted at the highest point in the vault?
      1. If yes, move to Step 3.
      2. If no, relocate the antenna to the highest point in the vault and Step 3.
    5. Is the antenna SMA connector corroded?
      • If yes, move to Step 4.
      • If no, continue to Step 3.

     

    Step 3: Swipe a magnet along the FM200 serial number barcode

    1. Listen for a series of error beeps. Wait approximately 5 minutes
      • Did you hear a series of error beeps?
        • If yes, see the chart below for the next steps
        • If no, continue to step 3-B
    1. Complete a communication Signal Test in the FM200 Activator
    1. Verify communication Signal Test in the FM200 Activator
      • Did the device communicate?
        • If yes, continue to Step 3-D
        • If no, continue to Step 4
    2. Verify battery level in the FM200 Activator.
      • Does the battery level have a green check mark?
        • If yes, complete the forms and depart the site.
        • If no, continue to Step 5.

     

    Step 4: Replace the antenna

    1. Install a new antenna in a plastic valve box outside of the utility vault.
      • FM200 Antenna Extension Guide: COMING SOON
    1. Connect the antenna to the flow monitor. Firmly hand tighten.
    2. Complete a communication Signal Test in the FM200 Activator.
    1. Verify communication in the FM200 Activator.
      • Did the device communicate?
        • If yes, complete the forms and depart the site.
        • If no, continue to step 4.

     

    Step 5: Replace the FM200 device.

    DO NOT replace the device BEFORE completing steps 1-4.

    1. Install a new FM200 flow monitor.
    2. Complete the Device Replacement Form
    3. Return the old FM200 flow monitor via RMA. Do not discard the device.

     

    Error Code Beeps

    Confirm the error code by swiping the magnet once again. Carefully listen for the total number of beeps emitted by the device. The beeps will occur in rapid succession. Additionally, the beeps emitted from the device will have a different tone from the beeps heard during the installation process. As a reminder, it may take up to 5 minutes for the device to generate and emit the error. Please be patient.

    2 Beeps

    Server or network error, try again in 5 minutes. Call contractor support after 3 attempts.

    3 Beeps

    Server error, try again in 5 minutes. Call contractor support after 3 attempts.

    4 Beeps

    Network error, try again in 5 minutes. Call contractor support after 3 attempts.

    5 Beeps

    Antenna-related, troubleshoot antenna connection and signal strength, try again.

    6 Beeps

    No response from the modem. Continue to Step 5 - Replace the FM200 device.


     

    Related Articles