    No Flow or Incorrect Flow Value

    Baseline Internal: Flow Troubleshooting

    PDF es:

    Table of Contents

    Incorrect Flow Value 

    If the controller is reporting an incorrect flow value, make sure the K-value is correct. 




    No Flow 

    If the controller is reporting No Flow:

    1.  Verify that water is actually flowing. 

    • Manually run a valve and visually confirm that water is flowing

    2.  Verify the wiring. 

    • Refer to the installation guide
    • Every flow sensor is different so be sure to use the appropriate flow meter's documentation.

    3.  Test Flow biCoder by performing a Tap Test. 

    • Tap yellow and white wires together
    • Make sure the LED blinks
    • If it  fails, replace the Flow biCoder

    Note: In some cases it may be necessary to take the flow device, and biCoder to the controller to manually/self test it at the terminals by themselves to rule out wire path issues. When running a self test on that flow biCoder, activate the flow device/register to identify if the controller reads flow on the test screen. This resource gives further detail on how to use a magnet on Hydrometer registers.