Note
If the master valve decoder is not pre-programmed you will need to program it at the controller BEFORE wiring.
For instructions on how to program a master valve decoder, read: Programming a Master Valve Decoder.
1. Power off the 2-wire when installing devices. Leave 24 to 36 inches of slack on the 2-wire to allow for easy installation and maintenance.
2. Master valves can be located a maximum of 250ft from the decoder location by using additional 14 gauge wires.
3. Connect the orange wire to the pilot wire from the master valve and the white wire to the common wire from the master valve.
4. Connect the red and black wire from the decoder to the corresponding red and black wires on the 2-wire. It is critical that polarity be maintained.
Warning
The Decoder wires must not have electrical contact with the soil or water. All connections must use DBR/Y-6 or equivalent moisture-resistant connectors. Install all connections correctly. Damage to the system will occur if these specifications are not followed.


Principle Wiring Techniques

WeatherTRAK WT_Master Valve and Flow Sensor Deployment Options.pdf, WT_H2O 2Wire Decoder_Troubleshooting and Diagnostics Guide.pdf