The Baseline BL-5308 biCoder is a two-wire decoder that is designed to work with most flow sensors and flow meters that produce a pulsed output. The BL-5308 Flow biCoder transmits the pulse data between the flow device and a BaseStation controller.
A flow sensor or flow meter measures the movement of the water as it moves past a sensor, typically in pulses per gallon. Baseline BaseStation controllers convert the pulse reading into a gallons per minute value. The K-value and Offset account for the pipe size when calculating water usage.
Installation Instructions
1. Power off the two-wire during the installation of any two-wire device.
2. Install the BL-5308 Flow biCoder as close to the flow device as possible. Follow the flow meter manufacturer’s specifications for required straight pipe before and after the flow meter for accurate readings.
3. Connect the red and black wires from the BL-5308 Flow biCoder to the red and black wires from the two-wire field. Be sure to maintain polarity by connecting red to red and black to black. Use 3M™ DBR/Y-6 or equivalent moisture-resistant connectors for all of these connections. Leave 24 to 36 inches of slack on the two-wire to allow for easy installation and maintenance.
4. Depending on the flow device, connect the white, yellow, and blue wires from the BL-5308 Flow biCoder to the wires from the flow device. Use 3M™ DBR/Y-6 or equivalent moisture-resistant connectors for all of these connections.
- For devices with two wires, see Diagram A below:
- For devices with three wires, see Diagram B below:
5. Verify communications from the BaseStation to the Flow biCoder and complete configuration and setup according to the instructions in the controller’s user manual.